Branch Circuits & WiringQuestion 231 of 521

A 240 V single-phase circuit uses 10 AWG copper (10,380 cmil) carrying 24 A over a one-way length of 150 ft, with K = 12.9. What is the approximate voltage drop and percentage?

a.4.5 V, about 1.9%
b.17.9 V, about 7.5%
c.8.9 V, about 3.7%
d.2.2 V, about 0.9%

Explanation

VD = 2 × 12.9 × 24 × 150 ÷ 10,380 = 92,880 ÷ 10,380 ≈ 8.9 V, which is 8.9/240 ≈ 3.7%. The other options misplace the length, current, or divide by the wrong circular-mil value.