Branch Circuits & WiringQuestion 231 of 521
A 240 V single-phase circuit uses 10 AWG copper (10,380 cmil) carrying 24 A over a one-way length of 150 ft, with K = 12.9. What is the approximate voltage drop and percentage?
a.4.5 V, about 1.9%
b.17.9 V, about 7.5%
c.8.9 V, about 3.7%
d.2.2 V, about 0.9%
Explanation
VD = 2 × 12.9 × 24 × 150 ÷ 10,380 = 92,880 ÷ 10,380 ≈ 8.9 V, which is 8.9/240 ≈ 3.7%. The other options misplace the length, current, or divide by the wrong circular-mil value.
Practice all 521 questions free — no signup required.
Related questions on this topic
- For the combined feeder plus branch circuit, the NEC informational note recommends total voltage drop not exceed what percentage?
- A 120 V single-phase circuit uses 12 AWG copper (6,530 cmil) carrying 20 A over a one-way length of 100 ft. Using VD = 2 × K × I × L ÷ cmil with K = 12.9, what is the approximate voltage drop?
- The circuit in the previous scenario has a voltage drop of about 6.6%, well above the recommended 3% for a branch circuit. What is the most appropriate corrective action?
- In the voltage-drop formula for a balanced 3-phase circuit, which multiplier replaces the factor of 2 used in single-phase calculations?
- To reduce voltage drop on a long branch-circuit run without changing the load, what is the most effective method?
- If the one-way length of a circuit run is doubled while current and conductor size stay the same, what happens to the voltage drop?