For the 50 HP, 460 V motor (FLC 65 A), what is the maximum inverse-time circuit breaker per the 250% column of Table 430.52?

a.162.5 A
b.113.75 A
c.195 A
d.520 A

Explanation

Inverse-time breaker: 250% of FLC = 65 x 2.50 = 162.5 A (then next-standard-size rule may apply). 113.75 A is 175% (dual-element fuse), 195 A is 300% (nontime-delay fuse), and 520 A is 800% (instantaneous trip).

Law Reference: 2023 NEC §430.52