Equipment & SystemsQuestion 301 of 521

For a permanently installed swimming pool, what conductor is required for the equipotential bonding grid?

a.No. 10 AWG stranded copper
b.No. 8 AWG solid copper
c.No. 6 AWG solid aluminum
d.No. 12 AWG insulated copper

Explanation

Section 680.26(B) requires the equipotential bonding to be established with a minimum No. 8 AWG solid copper conductor. Aluminum is not permitted in contact with pool structures, and conductors smaller than 8 AWG or stranded are not accepted for the bonding grid.

Law Reference: 2023 NEC §680.26

Practice all 521 questions free — no signup required.