Planning & EstimatingQuestion 376 of 521
A household range has a calculated demand of 8,000 VA. What maximum value may be used for the neutral (grounded) feeder load for this range?
a.5,600 VA
b.8,000 VA
c.4,000 VA
d.2,800 VA
Explanation
The neutral load for a household range may be taken at 70% of the demand: 8,000 × 0.70 = 5,600 VA. Using the full 8,000 VA ignores the 70% allowance, and the other values apply wrong percentages.
Law Reference: 2023 NEC §220.61(B)Practice all 521 questions free — no signup required.