Planning & EstimatingQuestion 407 of 521

Using the optional method, a dwelling's 220.82(B) loads compute to 19,280 VA, plus 5,000 VA of air conditioning at 100%. On a 240 V service (about 101 A), what is the minimum standard service size?

a.100 A
b.150 A
c.175 A
d.125 A

Explanation

Total = 19,280 + 5,000 = 24,280 VA; 24,280 ÷ 240 = 101 A. Since the demand exceeds 100 A, the next standard size, 125 A, is required. A 100 A service would be slightly undersized.

Law Reference: 2023 NEC §220.82