Services & DistributionQuestion 60 of 521
A feeder is protected by a 60 A overcurrent device. Per Table 250.122, what is the minimum copper EGC?
a.12 AWG
b.10 AWG
c.8 AWG
d.6 AWG
Explanation
Table 250.122 requires a 10 AWG copper EGC for overcurrent devices from 40 A up to and including 60 A. 12 AWG serves only up to 20 A, and 8 AWG/6 AWG are for 100 A/200 A respectively.
Law Reference: 2023 NEC §250.122Practice all 521 questions free — no signup required.