A feeder has a maximum unbalanced (neutral) load of 250 A. Applying the neutral demand provisions, the minimum neutral conductor ampacity is:

a.175 A
b.200 A
c.250 A
d.235 A

Explanation

Per 220.61(B), the first 200 A of unbalanced load is at 100% and the portion above 200 A may be taken at 70%: 200 + (50 x 0.70) = 235 A. Sizing at the full 250 A ignores the permitted demand, and 175 A/200 A understate the required capacity.

Law Reference: 2023 NEC §220.61