On a fixed-orifice (piston) system, which method is generally used to check the charge?
a.Subcooling only
b.The superheat method using target superheat charts
c.Weighing the compressor
d.Measuring duct static pressure
Explanation
Fixed-orifice metering devices are charged by the superheat method, comparing measured superheat to a target based on indoor wet-bulb and outdoor dry-bulb temperatures. TXV systems, by contrast, are typically charged by subcooling. Using the correct method for the metering device is essential.
Practice all 110 questions free — no signup required.
Related questions on this topic
- A technician measures a suction pressure whose saturation temperature is 40 F and a suction line temperature of 52 F. What is the superheat?
- Subcooling is measured at which point in the system?
- On a system with a condensing saturation temperature of 105 F and a liquid line temperature of 95 F, what is the subcooling?
- Under EPA Section 608, what must a technician do with refrigerant before opening most systems for service?
- EPA Section 608 certification is required for technicians who do what?
- Evacuating a system with a vacuum pump primarily removes what?