Drainage, Waste & VentQuestion 108 of 360
A 2 inch building drain sloped at 1/4 inch per foot is permitted a maximum load of how many DFU?
a.26 DFU
b.24 DFU
c.6 DFU
d.21 DFU
Explanation
Table 703.2 permits a 2 inch building drain at 1/4 inch per foot to carry 21 DFU. At 1/2 inch per foot the same pipe carries 26 DFU. The 24 value corresponds to a 2-1/2 inch drain, and 6 DFU is the branch capacity of a 2 inch fixture branch, not the building-drain load.
Law Reference: 2022 California Plumbing Code (CPC) §703.0 (Table 703.2)Practice all 360 questions free — no signup required.
Related questions on this topic
- The horizontal drainage pipe between a fixture trap and its vent is called the:
- A 5 inch building sewer sloped at 1/4 inch per foot is permitted a maximum load of how many DFU?
- A 6 inch building drain sloped at 1/8 inch per foot is permitted a maximum load of how many DFU?
- Loss of a trap seal from siphonage or back pressure is primarily prevented by:
- Developed length of a pipe run is measured as:
- In a wet-vented bathroom group, a wet-vent section carrying 4 DFU must be at least what size?