Gas PipingQuestion 245 of 360
Where should the sediment trap be installed in relation to the appliance shutoff valve and the appliance gas control?
a.Upstream of the shutoff valve, near the meter
b.Anywhere on the branch is fine
c.Only inside the appliance cabinet
d.Downstream of the shutoff valve and as close as practical to the appliance inlet, ahead of the gas control
Explanation
The sediment trap is placed downstream of the appliance shutoff valve and just ahead of the appliance gas control, as close as practical to the appliance inlet. In that position it can catch debris before the gas reaches the control valve. It is typically a tee with a short capped nipple pointing down.
Law Reference: California Plumbing Code, Fuel Gas provisionsPractice all 360 questions free — no signup required.
Related questions on this topic
- What is the typical operating (manifold) pressure for a standard residential propane (LP) appliance?
- Which statement about listed flexible appliance connectors is correct?
- A sizing table (0.5 psi drop, natural gas) shows that 3/4-inch schedule 40 pipe at a 40-foot run carries 170 cfh, and 1-inch pipe carries 320 cfh. A section must supply a 250,000 BTU/hr load over that 40-foot run. What is the smallest listed size that works?
- What is a common standard delivery pressure of natural gas to a typical single-family residence downstream of the utility meter?
- Low gas pressures for appliances are commonly expressed in inches of water column. Which instrument directly reads this pressure during setup and testing?
- When performing a gas piping pressure test, why should the test gauge have an appropriate scale for the test pressure?