Water Supply & DistributionQuestion 30 of 360
A pressure vacuum breaker (PVB) is selected for a landscape irrigation system. What is the minimum installation height for a PVB relative to the highest downstream head or outlet?
a.At least 6 inches above
b.At least 12 inches above
c.At the same level
d.Below the outlet is acceptable
Explanation
A PVB must be installed at least 12 inches above the highest downstream outlet or head so the air inlet can function during back-siphonage. Six inches is the AVB minimum, and installing at or below the highest outlet defeats the vacuum-breaking action.
Law Reference: 2022 California Plumbing Code (CPC) §603.0Practice all 360 questions free — no signup required.
Related questions on this topic
- Converting demand: a building has an estimated 46 WSFU load served predominantly by flush tanks. Using a typical Hunter-curve conversion, the demand is about 30 gpm. If you must maintain roughly 8 fps maximum velocity, why can you not simply pick the smallest pipe that carries 30 gpm at any velocity?
- Which standard covers seamless copper water tube types K, L, and M?
- On which fixtures does the code most specifically require water hammer arrestors?
- Two fixtures on a branch each require 4 gpm. If the branch is sized so the combined design demand (with diversity) is about 6 gpm rather than 8 gpm, what principle is being applied?
- For vertical copper water tube, how must risers be supported according to the support requirements?
- A commercial building connects to a boiler that uses chemical additives and is served from the potable main. What premise-isolation protection does the code generally require at the service?
Last reviewed: · editorial process
PrepPass Editorial Team · Verified against California CSLB C-36 Plumbing Trade Examination · How we review