An atmospheric vacuum breaker (AVB) is installed to protect a hose connection. What installation condition must be satisfied for an AVB to be used correctly?

a.It must be installed at least 6 inches above the highest downstream outlet or flood-level rim and never under continuous pressure
b.It may be installed below the flood-level rim
c.It may remain pressurized more than 12 hours continuously
d.It protects against backpressure

Explanation

An AVB must be installed a minimum of 6 inches above the flood-level rim or highest downstream outlet and cannot be under continuous pressure (more than 12 hours). It offers no backpressure protection and cannot be located below the flood-level rim, so those options are incorrect.

Law Reference: 2022 California Plumbing Code (CPC) §603.0