Drainage, Waste & VentQuestion 67 of 360
What is the minimum clearance required in front of a cleanout on a 4 inch drainage pipe?
a.12 inches
b.24 inches
c.18 inches
d.30 inches
Explanation
Cleanouts on pipe 3 inches and larger require a minimum clearance of 18 inches in front of the cleanout for rodding. Cleanouts on pipe smaller than 3 inches require only 12 inches. The 24 and 30 inch figures are more than the code minimum.
Law Reference: 2022 California Plumbing Code (CPC) §707.9Practice all 360 questions free — no signup required.