Code Admin & SafetyQuestion 109 of 110
Service equipment (other than dwellings) must be field marked with what value related to fault protection?
a.Maximum available fault current
b.The panel interrupting rating only
c.Installation date only
d.Phase rotation
Explanation
Service equipment must be legibly field marked with the maximum available fault current and the date of the calculation.