CalculationsQuestion 11 of 110

For a 200-A dwelling service using the 83% conductor allowance, what is the smallest copper ungrounded conductor (75 C) permitted for the main power feeder?

a.#3/0 AWG
b.#1/0 AWG
c.#2/0 AWG
d.#4/0 AWG

Explanation

200 A x 0.83 = 166 A required ampacity. At 75 C, #2/0 Cu is rated 175 A, which satisfies 166 A, so #2/0 is the smallest permitted.

Law Reference: 2023 NEC 310.12