CalculationsQuestion 16 of 110

For a motor with a 34-A full-load current, what is the maximum inverse-time circuit breaker for branch-circuit short-circuit and ground-fault protection (250%, then next higher standard size)?

a.70 A
b.80 A
c.100 A
d.90 A

Explanation

Inverse-time breaker: 250% of FLC = 34 x 2.50 = 85 A. Where this does not correspond to a standard size, the next higher standard rating (90 A) is permitted.

Law Reference: 2023 NEC 430.52