Services & DistributionQuestion 50 of 110

Generator output conductors must have an ampacity of at least what percent of the nameplate current?

a.100%
b.115%
c.125%
d.110%

Explanation

Generator conductors from the terminals to the first overcurrent device must be at least 115% of the nameplate current rating.

Law Reference: 2023 NEC 445.13