Advanced WiringQuestion 66 of 110

A hermetic compressor has a rated-load current of 24 A. What is the maximum branch-circuit short-circuit and ground-fault device at 175% (next standard size)?

a.40 A
b.45 A
c.50 A
d.60 A

Explanation

175% of 24 A = 42 A; the next standard overcurrent size is 45 A, which is the maximum permitted for short-circuit/ground-fault protection.

Law Reference: 2023 NEC 440.22(A)

Practice all 110 questions free — no signup required.

Related questions on this topic

Last reviewed: · editorial process

PrepPass Editorial Team · Verified against Master Electrician Licensing Exam (NEC-based) · How we review