Code Admin & SafetyQuestion 99 of 110
The dedicated equipment space above a panelboard extends how far above the equipment (or to a structural ceiling if lower)?
a.3 ft
b.4.5 ft
c.6 ft
d.7 ft
Explanation
The dedicated electrical space extends from the equipment to 6 ft above it, or to a structural ceiling if lower, and must be kept clear of foreign systems.
Law Reference: 2023 NEC 110.26(E)(1)Practice all 110 questions free — no signup required.