Systems & CodeQuestion 43 of 110

In a medical gas piping system, oxygen and other medical gases must use tubing that is cleaned and labeled for the service. What copper tubing is required for medical gas distribution?

a.Type M copper, brazed
b.PVC schedule 40
c.Type L or K copper, cleaned for oxygen service, brazed with joints purged with nitrogen
d.Galvanized steel, threaded

Explanation

Medical gas distribution uses type L or K copper specifically cleaned and capped for oxygen service, brazed with a nitrogen purge to prevent internal oxide (copper scale) formation. The nitrogen purge keeps the interior clean so particles cannot enter patient equipment. Type M, plastic, and threaded steel are all prohibited for medical gas.

Law Reference: NFPA 99

Practice all 110 questions free — no signup required.

Related questions on this topic

Last reviewed: · editorial process

PrepPass Editorial Team · Verified against Master Plumber Licensing Exam (UPC/IPC-based) · How we review