Systems & CodeQuestion 43 of 110
In a medical gas piping system, oxygen and other medical gases must use tubing that is cleaned and labeled for the service. What copper tubing is required for medical gas distribution?
a.Type M copper, brazed
b.PVC schedule 40
c.Type L or K copper, cleaned for oxygen service, brazed with joints purged with nitrogen
d.Galvanized steel, threaded
Explanation
Medical gas distribution uses type L or K copper specifically cleaned and capped for oxygen service, brazed with a nitrogen purge to prevent internal oxide (copper scale) formation. The nitrogen purge keeps the interior clean so particles cannot enter patient equipment. Type M, plastic, and threaded steel are all prohibited for medical gas.
Law Reference: NFPA 99Practice all 110 questions free — no signup required.
Related questions on this topic
- A reduced-pressure principle (RP) backflow assembly is installed on a service subject to a health hazard. How must it be installed with respect to the ground and drainage?
- A lawn irrigation system with chemical injection is connected to a potable supply. This is classified as a high health hazard under backpressure and backsiphonage conditions. Which backflow assembly is required?
- An air gap is used to protect a potable outlet discharging over a flood-level rim. What is the minimum air gap for an effective opening of 1 in diameter, using the rule of two times the effective opening?
- Medical gas piping must be tested before use. Which test verifies the system is free of leaks and cross connections at operating conditions?
- A water softener regenerates using 8 lb of salt per cubic foot of resin for a 3 cubic foot resin bed. How much salt is consumed per regeneration cycle?
- A water heater is installed in a garage where flammable vapors may be present. What installation requirement addresses ignition of those vapors?
Last reviewed: · editorial process
PrepPass Editorial Team · Verified against Master Plumber Licensing Exam (UPC/IPC-based) · How we review