Gas & FuelQuestion 62 of 110
Appliance venting is classified by category. A Category I appliance is best described as which of the following?
a.Positive vent pressure, non-condensing
b.Negative vent pressure, non-condensing (draft hood or fan-assisted, standard flue)
c.Positive vent pressure, condensing
d.Negative vent pressure, condensing
Explanation
A Category I appliance operates with a non-positive (negative) vent pressure and a non-condensing flue, so it uses a conventional type B vent or masonry chimney with natural or fan-assisted draft. Category IV is positive-pressure and condensing, requiring sealed plastic venting. Matching the vent material and pressure rating to the category is essential to avoid condensation damage or spillage.
Law Reference: IFGC §503.0Practice all 110 questions free — no signup required.
Related questions on this topic
- A gas system serves a longest run of 80 ft to the most remote appliance, which needs 90 cfh. The table for 80 ft gives 3/4 in = 82 cfh and 1 in = 155 cfh. What size serves that final branch?
- An appliance room contains a 120,000 BTU/hr furnace and a 40,000 BTU/hr water heater drawing combustion air from inside. Using the rule of 50 cubic feet of room volume per 1,000 BTU/hr for indoor air, what minimum room volume is required?
- Combustion air is taken from outdoors using two openings, one high and one low. The rule is 1 square inch of free area per 4,000 BTU/hr for each opening when using direct outdoor openings. For a 200,000 BTU/hr appliance load, what is the minimum free area of each opening?
- A high-efficiency condensing furnace exhausts cool, wet flue gas under positive pressure. What venting category and material are appropriate?
- Corrugated stainless steel tubing (CSST) must be electrically bonded to reduce the risk of arcing from a lightning-induced surge. Where is the bonding clamp attached?
- A newly installed natural-gas piping system is pressure tested before being placed in service. A common test is 3 psi (or 1.5 times working pressure, whichever is greater) held for a set duration. For low-pressure residential piping, what is a typical minimum test pressure and duration?