A service uses 3/0 AWG copper ungrounded service-entrance conductors. What is the minimum size copper grounding electrode conductor?

a.4 AWG
b.6 AWG
c.2 AWG
d.1/0 AWG

解析

Table 250.66 groups 2/0 and 3/0 copper service conductors together and calls for a 4 AWG copper grounding electrode conductor. The 6 AWG row applies to service conductors of 1 or 1/0 AWG, 2 AWG copper is required only above 3/0 through 350 kcmil, and 1/0 applies to service conductors above 350 through 600 kcmil.

法律依据: 2023 NEC Table 250.66