Where the grounding electrode conductor connects only to a driven ground rod, what is the largest size it is required to be?

a.2 AWG copper
b.4 AWG copper
c.6 AWG copper
d.1/0 AWG copper

解析

A rod, pipe or plate electrode has a limited earth contact area, so the conductor to it is never required to be larger than 6 AWG copper regardless of what Table 250.66 would otherwise demand. The 4 AWG limit applies to a concrete-encased electrode, and larger sizes are not required for any rod connection.

法律依据: 2023 NEC §250.66(A)