Under typical residential conditions, a 14 AWG copper conductor is generally protected at a MAXIMUM overcurrent device rating of:
a.15 amperes
b.20 amperes
c.25 amperes
d.30 amperes
Explanation
A 14 AWG copper conductor is normally limited to a 15-amp overcurrent device. 20 amps corresponds to 12 AWG and 30 amps to 10 AWG copper; protecting 14 AWG at those higher ratings would allow the wire to overheat before the breaker trips.
Law Reference: 2025 CA Electrical Code, Article 240 (Overcurrent Protection)Practice all 700 questions free — no signup required.