When 7 current-carrying conductors are bundled together in a single raceway, their allowable ampacity must be adjusted to what percent of the base value?
a.100 percent
b.90 percent
c.80 percent
d.70 percent
Explanation
For 7 through 9 current-carrying conductors the adjustment factor is 70 percent, because heat cannot dissipate as readily when many conductors share a raceway. 100, 90, and 80 percent apply to fewer conductors (3 or fewer, 4 to 6, respectively).
Law Reference: 2025 CA Electrical Code (CEC) §310.15 (Conductor Ampacity)Practice all 700 questions free — no signup required.
Related questions on this topic
- Along a kitchen countertop, receptacle outlets must be placed so that no point along the counter wall line is more than what distance from a receptacle?
- What is the MINIMUM headroom (vertical clearance) required for the working space about a service panel or other electrical equipment rated 600 volts or less?
- A feeder must supply a continuous load of 32 amperes plus a noncontinuous load of 40 amperes. What is the MINIMUM feeder conductor ampacity required?
- In a dwelling, 125-volt receptacles must have GFCI protection when installed within what distance of the outside edge of a kitchen or wet-bar sink?
- Which of the following branch circuits is MOST clearly required to have arc-fault circuit-interrupter (AFCI) protection?
- A device box contains four 12 AWG circuit conductors, two 12 AWG equipment grounding conductors, and one duplex receptacle. Using 2.25 cubic inches per 12 AWG conductor, what MINIMUM box volume is required?
Last reviewed: · editorial process
PrepPass Editorial Team · Verified against California CSLB General Building (B) Trade Examination · How we review