Core TradesQuestion 20 of 700
In a dwelling, 125-volt receptacles must have GFCI protection when installed within what distance of the outside edge of a kitchen or wet-bar sink?
a.3 feet
b.6 feet
c.8 feet
d.10 feet
Explanation
Receptacles within 6 feet of the outside edge of a sink require GFCI protection because of the shock hazard near water. 3 feet is too short, and 8 or 10 feet exceed the code trigger distance.
Law Reference: 2025 CA Electrical Code (CEC) Art. 210 (GFCI Protection)Practice all 700 questions free — no signup required.
Related questions on this topic
- What is the MINIMUM headroom (vertical clearance) required for the working space about a service panel or other electrical equipment rated 600 volts or less?
- A feeder must supply a continuous load of 32 amperes plus a noncontinuous load of 40 amperes. What is the MINIMUM feeder conductor ampacity required?
- When 7 current-carrying conductors are bundled together in a single raceway, their allowable ampacity must be adjusted to what percent of the base value?
- Which of the following branch circuits is MOST clearly required to have arc-fault circuit-interrupter (AFCI) protection?
- A device box contains four 12 AWG circuit conductors, two 12 AWG equipment grounding conductors, and one duplex receptacle. Using 2.25 cubic inches per 12 AWG conductor, what MINIMUM box volume is required?
- A 240-volt, 30-ampere dedicated circuit is wired with copper conductors. Under typical residential conditions, what is the MINIMUM copper conductor size that matches this 30-ampere circuit?