CALCULATION: A room measures 20 ft by 15 ft with a 10-ft ceiling. A ventilation system supplies 500 cubic feet per minute (CFM). Approximately how many air changes per hour (ACH) does this provide?
a.5 ACH
b.10 ACH
c.15 ACH
d.20 ACH
Explanation
Room volume = 20 x 15 x 10 = 3,000 cubic feet. Air per hour = 500 CFM x 60 = 30,000 cubic feet. ACH = 30,000 / 3,000 = 10. Answer 5 forgets the x60 factor properly; 15 and 20 use wrong volume.
Law Reference: 2025 CA Mechanical CodePractice all 700 questions free — no signup required.
Related questions on this topic
- CALCULATION: A common rule of thumb provides 1 square inch of combustion air opening per 1,000 Btu/h of appliance input when air comes from inside a large space. For a 100,000 Btu/h furnace using two openings (high and low), what free area does EACH opening need under this rule?
- A large commercial kitchen exhaust hood removes a high volume of air. Without makeup air, the space goes into strong negative pressure. The BEST solution is to:
- During a split-system AC installation, the refrigerant line set is run with several tight kinks and an excessively long distance beyond the manufacturer's limit. The MOST likely result is:
- A clothes dryer exhaust duct is run with several sharp bends and a long concealed length, then vented into an attic. Two problems with this install are:
- A high-efficiency (condensing) furnace produces acidic condensate. This condensate must be:
- Supply and return ducts installed in an unconditioned attic are typically required to be insulated and sealed MAINLY to:
Last reviewed: · editorial process
PrepPass Editorial Team · Verified against California CSLB General Building (B) Trade Examination · How we review