A service raceway enters a building from an underground distribution system. To prevent moisture and gases from entering, the raceway must be:
a.Left open for drainage
b.Filled with concrete
c.Painted on the interior
d.Sealed with an approved material (though a drainage provision may still be provided)
Explanation
Per 230.8, a raceway entering from an underground distribution system must be sealed with an identified compound to block moisture and gases; spare or unused raceways must also be sealed. Leaving it open or filling with concrete does not meet the sealing requirement, and painting does not seal against gas migration.
Law Reference: 2023 NEC §230.8Practice all 521 questions free — no signup required.
Related questions on this topic
- A separately derived system (such as the secondary of a transformer feeding a distribution panel) must have a system bonding jumper connecting:
- A detached garage is supplied by a feeder from the main dwelling. At the garage, the code generally requires:
- On a 4-wire delta system where the midpoint of one phase is grounded, the conductor with the higher voltage to ground (the high leg) must be durably and permanently marked, typically colored:
- Where multiple service disconnects are installed under the 2023 NEC, the general requirement (compared to older editions) is that they be:
- When installing a surge-protective device (SPD), the best practice for the connecting conductors is to:
- In a standard dwelling load calculation, the general lighting and receptacle load demand factor applies 100% to:
Last reviewed: · editorial process
PrepPass Editorial Team · Verified against California CSLB C-10 Electrical Trade Examination · How we review