In a standard dwelling load calculation, the general lighting and receptacle load demand factor applies 100% to:

a.The first 3000 VA
b.The first 10,000 VA
c.All VA above 120,000
d.None of the load

Explanation

Per Table 220.42, the first 3000 VA of general lighting/receptacle load is taken at 100%, the portion from 3001 to 120,000 VA at 35%, and any remainder at 25%. The other choices misstate the thresholds of the demand-factor table.

Law Reference: 2023 NEC §220.42