Services & DistributionQuestion 115 of 521

A series-rated combination of overcurrent devices is permitted to protect equipment where the available fault current exceeds the interrupting rating of a downstream device, provided the combination is:

a.Any two breakers from different manufacturers
b.Field-assembled without documentation
c.Rated only by adding the two interrupting ratings
d.Tested and marked/listed as a recognized series combination, and the equipment is field-marked accordingly

Explanation

Per 240.86, series ratings may be used only where the combination is listed and marked as a tested series combination (or engineered per 240.86(A)), and the end equipment is legibly field-marked to indicate the series-combination rating. Simply pairing arbitrary breakers or adding interrupting ratings is not permitted.

Law Reference: 2023 NEC §240.86

Practice all 521 questions free — no signup required.