A series-rated combination of overcurrent devices is permitted to protect equipment where the available fault current exceeds the interrupting rating of a downstream device, provided the combination is:
a.Any two breakers from different manufacturers
b.Field-assembled without documentation
c.Rated only by adding the two interrupting ratings
d.Tested and marked/listed as a recognized series combination, and the equipment is field-marked accordingly
Explanation
Per 240.86, series ratings may be used only where the combination is listed and marked as a tested series combination (or engineered per 240.86(A)), and the end equipment is legibly field-marked to indicate the series-combination rating. Simply pairing arbitrary breakers or adding interrupting ratings is not permitted.
Law Reference: 2023 NEC §240.86Practice all 521 questions free — no signup required.
Related questions on this topic
- A detached garage is supplied by a feeder from the main dwelling. At the garage, the code generally requires:
- On a 4-wire delta system where the midpoint of one phase is grounded, the conductor with the higher voltage to ground (the high leg) must be durably and permanently marked, typically colored:
- A service raceway enters a building from an underground distribution system. To prevent moisture and gases from entering, the raceway must be:
- Where multiple service disconnects are installed under the 2023 NEC, the general requirement (compared to older editions) is that they be:
- When installing a surge-protective device (SPD), the best practice for the connecting conductors is to:
- In a standard dwelling load calculation, the general lighting and receptacle load demand factor applies 100% to:
Last reviewed: · editorial process
PrepPass Editorial Team · Verified against California CSLB C-10 Electrical Trade Examination · How we review