Branch Circuits & WiringQuestion 141 of 521

Rigid metal conduit (RMC) must be securely fastened within what distance of each outlet box, junction box, or termination?

a.2 ft
b.3 ft
c.5 ft
d.6 ft

Explanation

Section 344.30(A) requires RMC to be securely fastened within 3 ft of each box, cabinet, or fitting. Support intervals along the run then follow Table 344.30(B). 2 ft is stricter than the code minimum, while 5 and 6 ft exceed the required fastening distance.

Law Reference: 2023 NEC §344.30(A)

Practice all 521 questions free — no signup required.