Branch Circuits & WiringQuestion 138 of 521

Between pull points (for example, from box to box), the total number of bends in one run of EMT must not exceed the equivalent of how many degrees?

a.180
b.270
c.360
d.450

Explanation

Section 358.26 limits the total bends between pull points to the equivalent of four quarter bends, or 360 degrees. Exceeding this makes conductor pulling difficult and risks insulation damage. 180 and 270 are below the allowed total; 450 exceeds the code maximum.

Law Reference: 2023 NEC §358.26