Branch Circuits & WiringQuestion 135 of 521
What is the minimum height (headroom) of the working space about electrical equipment such as panelboards, generally required by 110.26?
a.6 ft
b.6 ft 2 in
c.6 ft 4 in
d.6 ft 6 in
Explanation
Section 110.26(A)(3) requires the working space to be clear and extend from the grade or floor to a height of 6.5 ft (6 ft 6 in) or the height of the equipment, whichever is greater. The lower heights listed do not satisfy the minimum headroom.
Law Reference: 2023 NEC §110.26(A)(3)Practice all 521 questions free — no signup required.
Related questions on this topic
- In a dwelling, a hallway of what length or more must have at least one receptacle outlet?
- What is the minimum depth of working space in front of electrical equipment operating at 0 to 150 volts to ground, where there are exposed live parts on one side and no live or grounded parts on the other (Condition 1)?
- The width of the working space in front of electrical equipment must be at least the width of the equipment or what minimum, whichever is greater?
- Electrical metallic tubing (EMT) must be securely fastened within what distance of each outlet box, junction box, or fitting?
- After the required fastening near boxes, EMT must be supported at intervals not exceeding what distance?
- Between pull points (for example, from box to box), the total number of bends in one run of EMT must not exceed the equivalent of how many degrees?