Branch Circuits & WiringQuestion 136 of 521
Electrical metallic tubing (EMT) must be securely fastened within what distance of each outlet box, junction box, or fitting?
a.3 ft
b.4 ft
c.5 ft
d.6 ft
Explanation
Section 358.30(A) requires EMT to be securely fastened in place within 3 ft of each box, cabinet, or termination. It must also be supported at intervals not exceeding 10 ft. 4, 5, and 6 ft all exceed the 3-ft fastening distance from boxes.
Law Reference: 2023 NEC §358.30(A)Practice all 521 questions free — no signup required.
Related questions on this topic
- What is the minimum depth of working space in front of electrical equipment operating at 0 to 150 volts to ground, where there are exposed live parts on one side and no live or grounded parts on the other (Condition 1)?
- The width of the working space in front of electrical equipment must be at least the width of the equipment or what minimum, whichever is greater?
- What is the minimum height (headroom) of the working space about electrical equipment such as panelboards, generally required by 110.26?
- After the required fastening near boxes, EMT must be supported at intervals not exceeding what distance?
- Between pull points (for example, from box to box), the total number of bends in one run of EMT must not exceed the equivalent of how many degrees?
- Liquidtight flexible metal conduit (LFMC) must be securely fastened within what distance of each box, cabinet, or fitting where the conduit is not fished?