Using the 75 C column of Table 310.16, what is the allowable ampacity of a 3/0 AWG copper conductor?
a.175 A
b.230 A
c.200 A
d.150 A
Explanation
Table 310.16 lists 200 A for 3/0 copper at 75 C. 175 A is 2/0 copper, 230 A is 4/0 copper, and 150 A is 1/0 copper at 75 C.
Law Reference: 2023 NEC §310.16Practice all 521 questions free — no signup required.
Related questions on this topic
- What is the general rule for the metal water piping system inside a building served by an electrical service?
- What is the function of the main bonding jumper at a service?
- Where two rod electrodes are used to meet the supplemental-electrode rule, what is the minimum spacing between them?
- What is the 75 C ampacity of a 4/0 AWG copper conductor per Table 310.16?
- At the 75 C column of Table 310.16, what is the ampacity of a 1/0 AWG copper conductor?
- A 4/0 AWG copper THHN conductor (90 C, base 260 A) is in an ambient of 45 C. Using the 0.87 correction factor, what is the corrected ampacity?