Services & DistributionQuestion 18 of 521

A 4/0 AWG copper THHN conductor (90 C, base 260 A) is in an ambient of 45 C. Using the 0.87 correction factor, what is the corrected ampacity?

a.226 A
b.247 A
c.195 A
d.260 A

Explanation

260 A x 0.87 = 226 A after applying the 41-45 C temperature-correction factor from Table 310.15(B) to the 90 C column. 260 A ignores correction, and the other values use wrong factors.

Law Reference: 2023 NEC §310.15(B)

Practice all 521 questions free — no signup required.

Related questions on this topic

Last reviewed: · editorial process

PrepPass Editorial Team · Verified against California CSLB C-10 Electrical Trade Examination · How we review