How many current-carrying conductors can be in a raceway before an adjustment (fill derating) factor must be applied?

a.More than 4
b.More than 3
c.More than 6
d.More than 9

Explanation

Per 310.15(C)(1), adjustment factors apply when there are more than 3 current-carrying conductors in a raceway or cable. The first threshold (4-6 conductors) triggers 80%; the higher counts have their own factors.

Law Reference: 2023 NEC §310.15(C)(1)