A feeder supplies a continuous load of 176 A. What minimum conductor ampacity (before derating) is required?

a.220 A
b.176 A
c.200 A
d.141 A

Explanation

Per 215.2(A)(1)/210.19, feeder conductors must be sized at 125% of the continuous load: 176 A x 1.25 = 220 A. Using 176 A ignores the 125% factor, and the other values misapply it.

Law Reference: 2023 NEC §215.2