What is the maximum overcurrent protection allowed for a 12 AWG copper conductor under the small-conductor rule?
a.20 A
b.25 A
c.30 A
d.15 A
Explanation
Per 240.4(D), 12 AWG copper is limited to 20 A regardless of its higher table ampacity. 15 A is the 14 AWG limit, and 25 A or 30 A exceed the small-conductor cap for 12 AWG.
Law Reference: 2023 NEC §240.4(D)Practice all 521 questions free — no signup required.
Related questions on this topic
- A feeder supplies a continuous load of 176 A. What minimum conductor ampacity (before derating) is required?
- Six 3 AWG THHN copper conductors (90 C ampacity 110 A) are in one raceway at 30 C ambient. After the fill adjustment, what is the derated ampacity?
- Using the 60 C column of Table 310.16, what is the ampacity of a 6 AWG copper conductor?
- Which of the following is NOT a standard ampere rating for a fuse or inverse-time breaker per 240.6(A)?
- A conductor has an allowable ampacity of 115 A that does not match a standard fuse size. The load is 112 A. What is the largest standard OCPD permitted?
- For circuits rated over 800 A, what is the rule for the overcurrent device relative to conductor ampacity?