A conductor has an allowable ampacity of 115 A that does not match a standard fuse size. The load is 112 A. What is the largest standard OCPD permitted?

a.110 A
b.125 A
c.115 A
d.150 A

Explanation

Per 240.4(B), when the conductor ampacity does not correspond to a standard rating and is 800 A or less, the next higher standard device (125 A) is permitted. 115 A is not a standard size, 110 A is unnecessarily lower, and 150 A skips past the next standard.

Law Reference: 2023 NEC §240.4(B)