For equipment terminals on a circuit rated 100 A or less (not marked otherwise), which temperature column must be used to size conductors?

a.90 C column
b.The highest column of the conductor insulation
c.75 C column always
d.60 C column

Explanation

Per 110.14(C)(1), for circuits rated 100 A or less or 14-1 AWG conductors, terminations are limited to the 60 C column unless the equipment is listed for higher. The 90 C column may be used only for correction/adjustment, never for final termination sizing.

Law Reference: 2023 NEC §110.14(C)