Branch Circuits & WiringQuestion 181 of 521

A 4" x 1-1/2" square box has a volume of 21.0 in³. With no clamps, devices, or other allowances, what is the maximum number of 14 AWG conductors permitted in the box?

a.10
b.9
c.11
d.8

Explanation

Each 14 AWG conductor requires a 2.00 in³ volume allowance from Table 314.16(B). 21.0 ÷ 2.00 = 10.5, and you round down to 10 conductors. Rounding up to 11 would exceed the box volume, and 9 or 8 understates the count.

Law Reference: 2023 NEC §314.16(B)