Branch Circuits & WiringQuestion 182 of 521

Using the same 21.0 in³ box with no other fill allowances, what is the maximum number of 12 AWG conductors permitted?

a.10
b.9
c.8
d.7

Explanation

Each 12 AWG conductor requires 2.25 in³ per Table 314.16(B). 21.0 ÷ 2.25 = 9.33, rounded down to 9 conductors. 10 would exceed the volume, and 8 or 7 undercounts.

Law Reference: 2023 NEC §314.16(B)

Practice all 521 questions free — no signup required.

Related questions on this topic

Last reviewed: · editorial process

PrepPass Editorial Team · Verified against California CSLB C-10 Electrical Trade Examination · How we review