Branch Circuits & WiringQuestion 185 of 521
A box contains three internal cable clamps. In the box-fill calculation, how many volume allowances do the clamps require in total?
a.1 (a single allowance)
b.3 (one per clamp)
c.0 (clamps are exempt)
d.6 (two per clamp)
Explanation
Per 314.16(B)(2), where one or more internal clamps are present, a single volume allowance is required based on the largest conductor in the box — not one per clamp. So three clamps still count as only one allowance.
Law Reference: 2023 NEC §314.16(B)(2)Practice all 521 questions free — no signup required.