Branch Circuits & WiringQuestion 187 of 521
A box contains five 12 AWG current-carrying conductors, one 12 AWG equipment grounding conductor, one internal cable clamp, and one switch on a yoke (all conductors 12 AWG). What total box volume is required?
a.18.00 in³
b.15.75 in³
c.20.25 in³
d.22.50 in³
Explanation
At 2.25 in³ each: five conductors = 11.25, EGCs (as one) = 2.25, clamp (as one) = 2.25, and the yoke = 2 × 2.25 = 4.50. Total = 11.25 + 2.25 + 2.25 + 4.50 = 20.25 in³. The other values omit one or more required allowances.
Law Reference: 2023 NEC §314.16(B)Practice all 521 questions free — no signup required.