Branch Circuits & WiringQuestion 186 of 521
A box has four 12 AWG equipment grounding conductors entering it. How are they counted in the box-fill calculation?
a.Each counts individually (four allowances)
b.All together count as a single volume allowance
c.They are never counted
d.They count as two allowances
Explanation
Per 314.16(B)(5), all equipment grounding conductors together count as a single volume allowance, based on the largest EGC present. Counting them individually overstates the fill, and they are not exempt from the calculation.
Law Reference: 2023 NEC §314.16(B)(5)Practice all 521 questions free — no signup required.