Branch Circuits & WiringQuestion 190 of 521

Per Chapter 9, Table 1, what is the maximum permitted conduit fill percentage when three or more conductors are installed in a raceway?

a.31%
b.40%
c.53%
d.60%

Explanation

Chapter 9, Table 1 limits fill to 40% for three or more conductors. 53% is the limit for a single conductor, 31% is for exactly two conductors, and 60% is not a code fill value.

Law Reference: 2023 NEC Chapter 9, Table 1