Branch Circuits & WiringQuestion 219 of 521

Per 334.30, Type NM cable must be secured and supported at intervals not exceeding what distance along the run?

a.3 ft (900 mm)
b.6 ft (1.8 m)
c.4-1/2 ft (1.4 m)
d.10 ft (3.0 m)

Explanation

Section 334.30 requires NM cable to be secured at intervals not exceeding 4-1/2 ft, and within 12 in of every box or fitting. 6 ft is the MC interval, while 3 ft and 10 ft are not NM support values.

Law Reference: 2023 NEC §334.30