Branch Circuits & WiringQuestion 222 of 521

Which statement about Type MC cable ampacity is correct?

a.Like NM, MC ampacity is limited to the 60°C column
b.MC ampacity may be based on the 75°C or 90°C rating of its conductors, subject to terminations
c.MC is always limited to the 75°C column
d.MC is always taken at the 90°C column regardless of terminations

Explanation

Per 330.80, MC cable ampacity follows 310.15 based on the conductor temperature rating (commonly 90°C for derating), then limited by the termination temperature per 110.14(C). Unlike NM, it is not capped at 60°C, but it is also not simply taken at 90°C at the terminals.

Law Reference: 2023 NEC §330.80