Equipment & SystemsQuestion 250 of 521

Which motor current rating is used to select the running overload (overcurrent) protection device?

a.The Table 430.250 full-load current
b.The motor nameplate full-load amperes
c.The locked-rotor current from Table 430.251
d.250% of the full-load current

Explanation

NEC 430.6(A)(2) and 430.32 base overload protection on the motor's nameplate full-load amperes, because overloads protect the actual motor. The table FLC is used for conductors and short-circuit protection, not overload sizing.

Law Reference: 2023 NEC §430.32